Tucker Road Ice Rink
Discipline:
ME & Structural Engineering
Oxon Hill, Maryland
Square Footage:
Lobby Area

Mechanical, electrical and structural engineering services for addition of air conditioning to the lobby area of an existing ice rink with an estimated occupancy of 150 people.
Performed heating and cooling load calculations for addition of a new 15 ton gas fired packaged roof top air conditioning unit.
Provided mechanical drawings showing the new roof top unit related ductwork and air distribution devices. The size and location of ductwork was field verified with the existing structural members, etc.
Extended propane gas piping from the existing main propane gas piping at the point of entry to the buildings.
Provided structural drawings showing the required modification to the existing roof structure in order to support the new roof top unit.
Calculated the spare electrical capacity available on the existing main electrical panel for serving the new roof mounted air conditioning unit.
Provided electrical engineering services for sizing the conduit, wiring, disconnect switch and circuit breaker serving the new roof mounted air conditioning unit.
Provided smoke detectors on the supply and return ductwork and connected to the building fire alarm system.
Performed of construction phase services consisted of review of shop drawings and preparation of field sketches.